Manufacturer: Yokogawa Electric Corporation
Yokogawa DCS CENTUM VP Analog Input Module AAV142
STANDARD SPECIFICATIONS
Current/Voltage Input Modules (Non-Isolated)
These modules mainly receive 4 to 20 mA DC or 1 to 5 V DC standardized signal from 2-wire/4-wire transmitters.
They can be used in dual redundant configuration. Yokogawa DCS CENTUM VP Analog Input Module AAV142
Items |
Specifications |
|||
Model |
AAI141 (*1) |
AAV141 |
AAV142 |
|
Number of input channels |
16, non-isolated |
16, non-isolated(differential input) |
16, non-isolated |
|
Input signal |
4 to 20 mA DC |
1 to 5 V DC(allowable common mode voltage ± 1 V or less) |
-10 to 10 V DC |
|
Allowable input current/voltage |
27 mA |
±7.5 V |
±13 V |
|
Withstanding voltage |
— |
— |
— |
|
Input resistance |
Power ON |
400 Ω (at 20 mA) to 1000 Ω(at 4 mA) (*2) |
1 MΩ or more |
1 MΩ or more |
Power OFF |
500 kΩ or more |
340 kΩ or more |
660 kΩ or more |
|
Accuracy |
±16 μA |
±4 mV |
±20 mV |
|
Data update period |
10 ms |
|||
Step response time |
100 ms |
|||
Transmitter power supply |
14.8 V or more (at 20 mA) (*3)26.4 V or less (at 0 mA)(output current limit: 27 mA) |
— |
— |
|
Setting of 2-wire or 4-wire transmitter |
For each channel by setting pin |
— |
— |
|
Drift due to ambient temperature change |
±16 μA/10 °C |
±4 mV/10 °C |
±20 mV/10 °C |
|
Maximum current consumption |
310 mA (5 V DC),450 mA (24 V DC) |
350 mA (5 V DC) |
350 mA (5 V DC) |
|
Weight |
0.2 kg |
0.2 kg |
0.2 kg |
|
External connection |
Pressure clamp terminal, KS cable, MIL connector cable |
|||
HART communication (*4) |
Available |
— |
— |
*1: This AAV142 does not allow a Zener barrier to be connected. If the module AAV142 is to be used in intrinsically safe applications, use an isolation barrier. Yokogawa DCS CENTUM VP Analog Input Module AAV142
*2: Viewed from the terminals, module input resistance is, depending on the current flowing:
250 Ω +(voltage drop (3 V maximum) in the input protection circuit)/(current value)
*3: This voltage is developed between connecting terminals for this module’s 2-wire transmitter. When calculating if transmitter minimum operating voltage requirement will be satisfied, remember to allow for voltage drop in external wiring.
*4: R3.02 or later version supports HART function. When installing the module AAV142 with HART function to a remote node, the firmware of EB401 must be Rev 2 or later.
For HART function specifications, refer to “HART Communication Package (for A□I□□□-H) (GS 33Q03L70-31E).”
Yokogawa DCS CENTUM VP Analog Input Module AAV142
MODELS AND SUFFIX CODES
|
|
Description |
Model |
AAV142 |
Analog Input Module (-10 to +10 V, 16-channel, Non-Isolated) |
Suffix Codes |
-S |
Standard type |
5 |
With no explosion protection |
|
E |
With explosion protection |
|
0 |
Basic type |
|
3 |
With ISA Standard G3 option and temperature (-20 to 70 °C) option |
|
Option Codes |
/K4A00 |
With KS Cable Interface Adapter [Model: ATK4A-00] |
/A4S00 |
With Pressure Clamp Terminal Block for Analog [Model: ATA4S-00] |
|
/A4S10 |
With Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4S-10] |
|
/A4D00 |
With Dual Pressure Clamp Terminal Block for Analog [Model: ATA4D-00] |
|
/A4D10 |
With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4D-10] |
|
/CCC01 |
With Connector Cover for MIL Cable [Model: ACCC01] |
- 询价产品:Yokogawa DCS CENTUM VP Analog Input Module AAV142 AAV142
- 询价数量: /个
- 联系人:
- 联系电话: