Yokogawa DCS CENTUM VP Analog Input Module AAI141
筛选
  • 地区
    全部
  • 会员级别
    全部
筛选
  • 截止时间
    全部
仪表展览网>产品库>Control System Parts
价格: 面议
产品型号:AAI141
公司名称:GUANGZHOU TAIKE ELECTRON TECHNOLOGY CO.,LTD.
所在地:广东广州
发布时间:2018-01-04
GUANGZHOU TAIKE ELECTRON TECHNOLOGY CO.,LTD.
产品简介
Yokogawa DCS CENTUM VP Analog Input Module AAI141, Yokogawa DCS CENTUM VP Analog Input Module AAI141. Yokogawa DCS. Favorable Price. Please contact us
产品详情

Manufacturer: Yokogawa Electric Corporation

Yokogawa DCS CENTUM VP Analog Input Module AAI141

AAI141 AAI141-S50


STANDARD SPECIFICATIONS

Current/Voltage Input Modules (Non-Isolated)

Yokogawa DCS CENTUM VP Analog Input Module AAI141

These modules mainly receive 4 to 20 mA DC or 1 to 5 V DC standardized signal from 2-wire/4-wire transmitters.

They can be used in dual redundant configuration.

Items

Specifications

Model

AAI141 (*1)

AAV141

AAV142

Number of input channels

16, non-isolated

16, non-isolated(differential input)

16, non-isolated

Input signal

4 to 20 mA DC

1 to 5 V DC(allowable common mode voltage ± 1 V or less)

-10 to 10 V DC

Allowable input current/voltage

27 mA

 ±7.5 V

±13 V

Withstanding voltage

 —

—

—

Input resistance

Power ON

400 Ω (at 20 mA) to 1000 Ω(at 4 mA) (*2)

1 MΩ or more

1 MΩ or more

Power OFF

 500 kΩ or more

340 kΩ or more

660 kΩ or more

Accuracy

 ±16 μA

±4 mV

 ±20 mV

Data update period

10 ms

Step response time

100 ms

Transmitter power supply

14.8 V or more (at 20 mA) (*3)26.4 V or less (at 0 mA)(output current limit: 27 mA)

—

 —

Setting of 2-wire or 4-wire transmitter

 For each channel by setting pin

 —

—

Drift due to ambient temperature change

±16 μA/10 °C

 ±4 mV/10 °C

 ±20 mV/10 °C

Maximum current consumption

310 mA (5 V DC),450 mA (24 V DC)

 350 mA (5 V DC)

350 mA (5 V DC)

Weight

0.2 kg

0.2 kg

0.2 kg

External connection

 Pressure clamp terminal, KS cable, MIL connector cable

HART communication (*4)

Available

 —

 —

*1: This Yokogawa Analog Input Module AAI141 does not allow a Zener barrier to be connected. If the module Yokogawa Analog Input Module AAI141 is to be used in intrinsically safe applications, use an isolation barrier.

*2: Viewed from the terminals, module input resistance is, depending on the current flowing:

250 Ω +(voltage drop (3 V maximum) in the input protection circuit)/(current value)

*3: This voltage is developed between connecting terminals for this module’s 2-wire transmitter. When calculating if transmitter minimum operating voltage requirement will be satisfied, remember to allow for voltage drop in external wiring.

*4: R3.02 or later version supports HART function. When installing the module with HART function to a remote node, the firmware of EB401 must be Rev 2 or later.

For HART function specifications, refer to “HART Communication Package (for A□I□□□-H) (GS 33Q03L70-31E).”

Yokogawa DCS CENTUM VP Analog Input Module AAI141

MODELS AND SUFFIX CODES

 

 

Description

Model

AAI141

Analog Input Module (4 to 20 mA, 16-channel, Non-Isolated)

Suffix Codes

-S

Standard type

-H

With digital communication (HART protocol)

5

With no explosion protection

E

With explosion protection

0

Basic type

3

With ISA Standard G3 option and temperature (-20 to 70 °C) option

Option Codes

/K4A00

With KS Cable Interface Adapter [Model: ATK4A-00]

/A4S00

With Pressure Clamp Terminal Block for Analog [Model: ATA4S-00]

/A4S10

With Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4S-10]

/A4D00

With Dual Pressure Clamp Terminal Block for Analog [Model: ATA4D-00]

/A4D10

With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4D-10]

/CCC01

With Connector Cover for MIL Cable [Model: ACCC01]

商铺其他产品
联系商家 立即询价
发布询价单