Manufacturer: Yokogawa Electric Corporation
Yokogawa Analog Input Module AAI143-S53
STANDARD SPECIFICATIONS
Current Input Modules (Isolated)
This module inputs 4 to 20 mA.
It can be used in dual redundant configuration.
Yokogawa Analog Input Module AAI143-S53
Items
Specifications
Model
AAI143 (*1)
Number of input channels
16, isolated
Input signal
4 to 20 mA
Allowable input current
24 mA
Withstanding voltage
Between input and system: 1500 V AC For 1
minute (*4)
Input resistance
Power ON
270 Ω (20 mA) to 350 Ω (4 mA) (*2)
Power OFF
500 kΩ or more
Accuracy
±16 μA
Data update period
10 ms
Transmitter power supply
19.0 V or more (at 20 mA) 25.5 V or less (at 0
mA) (output current limit: 25 mA) (*5)
Setting of 2-wire or 4-wire transmitter
For each channel by setting pin
Drift due to ambient temperature change
±16 μA/10˚C
Maximum current consumption
230 mA (5 V DC) , 540 mA (24 V DC)
Weight
0.3 kg
External communication
Pressure clamp terminal, MIL connector cable, Dedicated
cable (KS1)
HART communication (*3)
Available
*1: This module Yokogawa Analog Input Module AAI143-S53 does not allow a Zener barrier to be connected. If the module is to be used in intrinsically safe applications, use an isolation barrier.
*2: Viewed from the terminals, module input resistance is, depending on the current flowing:
250 Ω +( voltage drop (0.4 V maximum) in the input protection circuit)/(current value)
*3: When installing the module Yokogawa Analog Input Module AAI143-S53 with HART function to a remote node, the firmware of EB401 must be Rev 2 or later.For HART function specifications, refer to “HART Communication Package (for A□I□□□-H) (GS 33Q03L70-31E).”
*4: The withstanding voltage for using the dedicated cable is 500 V AC (between the input signal and the system).The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable.
*5: This voltage is developed between connecting terminals for this Yokogawa Analog Input Module AAI143-S53 module’s 2-wire transmitter. When calculating if transmitter minimum operating voltage requirement will be satisfied, remember to allow for voltage drop in external wiring.MODELS AND SUFFIX CODES
Yokogawa Analog Input Module AAI143-S53
Description
Model
AAI143
Analog
Input Module (4 to 20 mA, 16-channel, Isolated)
Suffix Codes
-S
Standard
type
-H
With
digital communication (HART protocol)
5
With no explosion
protection
E
With explosion
protection
0
Basic
type
3
With
ISA Standard G3 option and temperature (-20 to 70 °C) option
Option Codes
/K4A00
With
KS Cable Interface Adapter (For connecting AEA4D Terminal Board) [Model:
ATK4A-00]
/A4S00
With
Pressure Clamp Terminal Block [Model: ATA4S-00]
/A4S10
With
Pressure Clamp Terminal Block (surge absorber) [Model: ATA4S-10]
/A4D00
With
Dual Pressure Clamp Terminal Block [Model: ATA4D-00]
/A4D10
With
Dual Pressure Clamp Terminal Block (surge absorber) [Model: ATA4D-10]
/CCC01
With
Connector Cover for MIL Cable [Model: ACCC01]
- Yokogawa Field Control Unit AFV10S-S31151 AFV10S-S31151
- Yokogawa Field Control Unit AFV10S AFV10S
- Yokogawa ER Bus Interface Slave Module EB511-E1 EB511-E1
- Yokogawa ER Bus Interface Slave Module EB511-E0 EB511-E0
- Yokogawa ER Bus Interface Slave Module EB511-51 EB511-51
- Yokogawa ER Bus Interface Slave Module EB511 EB511